System Separator Type 575 BA Flange PN 10System Separator Type 575 BA Flange PN 10

7575 System Separator Type 575 BA Flange PN 10

Article No. DNPN
(bar)
H1H2Hø DLø BH3weight
(kg)
Availability watchlist
7575050000 50 10 129 108.5 382 50 302 169 13.200 on demand
7575065000 65 10 132.5 108.5 385 50 307 169 17.000 on demand
7575080000 80 10 170 115 484 80 470 169 26.500 on demand
7575100000 100 10 170 115 484 80 470 169 28.000 on demand
7575150000 150 10 310 229 839 90 600 294 300 103.000 on demand
7575200000 200 10 350 272 922 90 780 370 300 111.000 on demand
7575250000 250 10 350 272 922 90 930 436 300 142.000 on demand
DN
watchlist
7575050000 50
PN10 bar
H1129
H2108.5
H382
ø D50
L302
ø B169
H3
weight13.200 kg
Availabilityon demand
7575065000 65
PN10 bar
H1132.5
H2108.5
H385
ø D50
L307
ø B169
H3
weight17.000 kg
Availabilityon demand
7575080000 80
PN10 bar
H1170
H2115
H484
ø D80
L470
ø B169
H3
weight26.500 kg
Availabilityon demand
7575100000 100
PN10 bar
H1170
H2115
H484
ø D80
L470
ø B169
H3
weight28.000 kg
Availabilityon demand
7575150000 150
PN10 bar
H1310
H2229
H839
ø D90
L600
ø B294
H3300
weight103.000 kg
Availabilityon demand
7575200000 200
PN10 bar
H1350
H2272
H922
ø D90
L780
ø B370
H3300
weight111.000 kg
Availabilityon demand
7575250000 250
PN10 bar
H1350
H2272
H922
ø D90
L930
ø B436
H3300
weight142.000 kg
Availabilityon demand

Application

  • System separator with controllable differential pressure, Type BA
  • System separation of drinking water in systems such as chemical, car wash, disinfection, emergency cooling, sprinkler systems or entire drinking water systems.

Mode of operation

  • The system separator consists of three chambers, whereby the differential pressure in the direction of flow from the first to the third chamber must be at least 140 mbar higher. If this value is not reached, the drain valve opens and the water flows into the sewerage system instead of back into the drinking water network.

Design

  • Execution according to EN 1717 and EN 12729
  • Pressure: PN 10
  • Flange DN 50 to DN 100 Flange hole pattern PN 10 Gunmetal body and cover
  • Flange DN 150 to DN 250 Flange hole pattern PN 10 Body and cover made of spheroidal graphite cast iron
  • Minimum flow pressure 1.5 - 2 bar, max. flow velocity 3.0 m/s Operating pressure max. 10 bar
  • Medium temperature up to 65 °C

Installation and assembly

  • Shut–off valves should be fitted on both sides of the valve and a dirt trap should be installed on the inlet side of the valve.
  • The installation must be horizontal and should be carried out after the water meter.
  • The sewer connection must be large enough to ensure that the valve never comes to rest in the water, even in the event of flooding.
  • Type 575 BA system separators require maintenance in accordance with SVGW W3/E2.
more